ASHRAE Standard 90.1 2016 IP
$95.88
ASHRAE Standard 90.1-2016 (I-P Edition) — Energy Standard for Buildings Except Low-Rise Residential Buildings (ANSI Approved; IES Co-sponsored)
Published By | Publication Date | Number of Pages |
ASHRAE | 2016 |
Standard 90.1 has been a benchmark for commercial building energy codes in the United States and a key basis for codes and standards around the world for more than 35 years. This standard provides the minimum requirements for energy-efficient design of most buildings, except low-rise residential buildings. It offers, in detail, the minimum energy efficiency requirements for design and construction of new buildings and their systems, new portions of buildings and their systems, and new systems and equipment in existing buildings, as well as criteria for determining compliance with these requirements. It is an indispensable reference for engineers and other professionals involved in design of buildings and building systems. This 2016 edition comprises numerous energy-saving measures and incorporates changes from more than 125 addenda. It also includes the following: Format changes to improve usability and readability: One-column format for easier reading Exceptions separated, indented, and set apart with a smaller font size Italicized defined terms Changes to table formats to provide contrast between rows Structural changes: A new Reference Standard Reproduction Annex 1 is provided at the end of the document. Section 5.1.4 now cites ASHRAE Standard 169 as the source for climatic data, and Annex 1 contains extracts of tables and figures from that standard for the reader’s convenience. Two new climate zones (0A/B) have been added to all prescriptive requirements tables. Significant technical content changes: Building Envelope Envelope verification in support of reduced air infiltration and increased requirements for air leakage of overhead coiling doors. Increased stringency requirements for metal building roofs and walls, fenestration, and opaque doors. Improved clarity on defining exterior walls, building orientation, fault assumptions for the effective R-value of air spaces, and calculation procedures for insulating metal building walls. Lighting Modified requirements for exterior and interior lighting power densities to reflect new lighting levels in the IES Lighting Handbook. Modified requirements for lighting control to add additional controls in some space types and options to others to allow easier application of advanced controls. Mechanical Large, electrically driven chilled-water plants are now required to be monitored for electric energy use and efficiency. Dedicated outdoor air systems now include both efficiency and rating requirements for compliance. Requirements are introduced for designs to include both use category and efficiency class. Requirement that air-cooled DX cooling units with economizers have a monitoring system to determine that the air economizer is working properly. Energy Cost Budget (ECB) and Modeling Appendix G now can be used as a path for compliance with the standard. Changes to elevator, motor, and refrigeration baselines; changes to the baseline for existing building projects; and changes to specific opaque assemblies for the baseline envelope model. Modeling rule changes were made to heat pump auxiliary heat, economizer shutoff, lighting controls, humidification systems, cooling towers, and the simulation of preheat coils.
PDF Catalog
PDF Pages | PDF Title |
---|---|
1 | ANSI/ASHRAE/IES Standard 90.1-2016 (I-P Edition) |
5 | Contents |
7 | Foreword |
9 | 1. Purpose 1.1 |
11 | 2. Scope 2.1 2.2 2.3 2.4 |
13 | 3. Definitions, Abbreviations, and Acronyms 3.1 General 3.2 Definitions |
41 | 3.3 Abbreviations and Acronyms |
45 | 4. Administration and Enforcement 4.1 General 4.1.1 Scope 4.1.1.1 New Buildings 4.1.1.2 Additions to Existing Buildings 4.1.1.3 Alterations of Existing Buildings 4.1.1.4 Replacement of Portions of Existing Buildings 4.1.1.5 Changes in Space Conditioning 4.1.2 Administrative Requirements 4.1.3 Alternative Materials, Methods of Construction, or Design 4.1.4 Validity |
46 | 4.1.5 Other Laws 4.1.6 Referenced Standards 4.1.7 Normative Appendices 4.1.8 Informative Appendices 4.1.9 Reference Standard Reproduction Annexes 4.2 Compliance 4.2.1 Compliance Paths 4.2.1.1 New Buildings |
47 | 4.2.1.2 Additions to Existing Buildings 4.2.1.2.1 4.2.1.3 Alterations of Existing Buildings 4.2.2 Compliance Documentation 4.2.2.1 Construction Details 4.2.2.2 Supplemental Information |
48 | 4.2.2.3 Manuals 4.2.3 Labeling of Material and Equipment 4.2.4 Inspections 4.2.5 Verification and Commissioning Reporting 4.2.5.1 Nonconformance |
49 | 5. Building Envelope 5.1 General 5.1.1 Scope 5.1.2 Space-Conditioning Categories 5.1.2.1 5.1.2.2 5.1.2.3 5.1.3 Envelope Alterations |
50 | 5.1.4 Climate 5.1.4.1 United States Locations 5.1.4.2 International Locations 5.2 Compliance Paths 5.2.1 Compliance |
51 | 5.2.2 5.3 Simplified Building (Not Used) 5.4 Mandatory Provisions 5.4.1 Insulation 5.4.2 Fenestration and Doors 5.4.3 Air Leakage 5.4.3.1 Continuous Air Barrier 5.4.3.1.1 Continuous Air Barrier Design 5.4.3.1.2 Continuous Air Barrier Installation 5.4.3.1.3 Testing, Acceptable Materials, and Assemblies |
52 | 5.4.3.2 Fenestration and Doors |
53 | 5.4.3.3 Loading Dock Weatherseals 5.4.3.4 Vestibules |
54 | 5.4.3.4.1 5.5 Prescriptive Building Envelope Option 5.5.1 5.5.2 5.5.3 Opaque Areas 5.5.3.1 Roof Insulation 5.5.3.1.1 Roof Solar Reflectance and Thermal Emittance |
65 | 5.5.3.2 Above-Grade Wall Insulation 5.5.3.3 Below-Grade Wall Insulation 5.5.3.4 Floor Insulation 5.5.3.5 Slab-on-Grade Floor Insulation |
66 | 5.5.3.6 Opaque Doors 5.5.4 Fenestration 5.5.4.1 General 5.5.4.2 Fenestration Area 5.5.4.2.1 Vertical Fenestration Area 5.5.4.2.2 Maximum Skylight Fenestration Area 5.5.4.2.3 Minimum Skylight Fenestration Area |
67 | 5.5.4.3 Fenestration U-Factor 5.5.4.4 Fenestration Solar Heat Gain Coefficient (SHGC) 5.5.4.4.1 SHGC of Vertical Fenestration |
68 | 5.5.4.4.2 SHGC of Skylights |
69 | 5.5.4.5 Fenestration Orientation 5.5.4.6 Visible Transmittance/SHGC Ratio |
70 | 5.6 Building Envelope Trade-Off Option 5.6.1 5.6.1.1 5.6.1.2 Trade-Offs Limited to Building Permit 5.6.1.3 5.7 Submittals 5.7.1 General 5.7.2 Submittal Document Labeling of Space-Conditioning Categories 5.7.3 Visible Transmittance |
71 | 5.7.4 Submittal Documentation of Daylight Areas 5.8 Product Information and Installation Requirements 5.8.1 Insulation 5.8.1.1 Labeling of Building Envelope Insulation 5.8.1.2 Compliance with Manufacturers’ Requirements 5.8.1.3 Loose-Fill Insulation Limitation 5.8.1.4 Baffles 5.8.1.5 Substantial Contact 5.8.1.6 Recessed Equipment |
72 | 5.8.1.7 Insulation Protection 5.8.1.7.1 5.8.1.7.2 5.8.1.7.3 5.8.1.8 Location of Roof Insulation 5.8.1.9 Extent of Insulation 5.8.1.10 Joints in Rigid Insulation 5.8.2 Fenestration and Doors 5.8.2.1 Rating of Fenestration Products 5.8.2.2 Labeling of Fenestration and Door Products 5.8.2.3 U-Factor |
73 | 5.8.2.4 Solar Heat Gain Coefficient 5.8.2.5 Visible Transmittance 5.9 Inspection and Verification 5.9.1 Inspections 5.9.1.1 Inspection of Fenestration and Door Requirements 5.9.1.2 Inspection of Loading Dock Weatherseals 5.9.1.3 Inspection of Opaque Building Envelope Air Tightness Requirements 5.9.1.4 Fenestration Inspections |
74 | 5.9.2 Verification 5.9.2.1 Building Envelope Performance Verification 5.9.2.2 Air Leakage Verification |
75 | 6. Heating, Ventilating, and Air Conditioning 6.1 General 6.1.1 Scope 6.1.1.1 New Buildings 6.1.1.2 Additions to Existing Buildings 6.1.1.3 Alterations to Heating, Ventilating, Air Conditioning, and Refrigeration in Existing Buildings 6.1.1.3.1 |
76 | 6.1.1.3.2 6.1.1.3.3 6.1.1.3.4 6.1.1.3.5 6.1.2 Climate 6.2 Compliance Paths 6.2.1 Compliance 6.2.2 6.3 Simplified Approach Option for HVAC Systems |
77 | 6.3.1 Scope 6.3.2 Criteria |
78 | 6.4 Mandatory Provisions 6.4.1 Equipment Efficiencies, Verification, and Labeling Requirements 6.4.1.1 Minimum Equipment Efficiencies—Listed Equipment—Standard Rating and Operating Conditions |
79 | 6.4.1.2 Minimum Equipment Efficiencies—Listed Equipment—Nonstandard Conditions 6.4.1.2.1 Water-Cooled Centrifugal Chilling Packages |
80 | 6.4.1.2.2 Positive Displacement (Air- and Water-Cooled) Chilling Packages 6.4.1.3 Equipment Not Listed 6.4.1.4 Verification of Equipment Efficiencies |
81 | 6.4.1.5 Labeling 6.4.1.5.1 Mechanical Equipment 6.4.1.5.2 Packaged Terminal Air Conditioners 6.4.2 Calculations 6.4.2.1 Load Calculations 6.4.2.2 Pump Head 6.4.3 Controls and Diagnostics 6.4.3.1 Zone Thermostatic Controls 6.4.3.1.1 General 6.4.3.1.2 Dead Band 6.4.3.2 Set-Point Overlap Restriction |
82 | 6.4.3.3 Off-Hour Controls 6.4.3.3.1 Automatic Shutdown 6.4.3.3.2 Setback Controls 6.4.3.3.3 Optimum Start Controls 6.4.3.3.4 Zone Isolation |
83 | 6.4.3.3.5 Automatic Control of HVAC in Hotel/Motel Guest Rooms 6.4.3.3.5.1 Guest Room HVAC Set-Point Control 6.4.3.3.5.2 Guest Room Ventilation Control 6.4.3.3.5.3 Automatic Control |
84 | 6.4.3.4 Ventilation System Controls 6.4.3.4.1 Stair and Shaft Vents 6.4.3.4.2 Shutoff Damper Controls 6.4.3.4.3 Damper Leakage 6.4.3.4.4 Ventilation Fan Controls |
85 | 6.4.3.4.5 Enclosed Parking Garage Ventilation 6.4.3.5 Heat Pump Auxiliary Heat Control 6.4.3.6 Humidification and Dehumidification 6.4.3.7 Freeze Protection and Snow/Ice Melting Systems |
86 | 6.4.3.8 Ventilation Controls for High-Occupancy Areas 6.4.3.9 Heated or Cooled Vestibules 6.4.3.10 Direct Digital Control (DDC) Requirements 6.4.3.10.1 DDC Applications 6.4.3.10.2 DDC Controls |
87 | 6.4.3.10.3 DDC Display 6.4.3.11 Chilled-Water Plant Monitoring 6.4.3.11.1 Monitoring 6.4.3.11.2 Electric-Motor-Driven Chiller System Recording and Reporting 6.4.3.12 Economizer Fault Detection and Diagnostics (FDD) |
88 | 6.4.4 HVAC System Construction and Insulation 6.4.4.1 Insulation 6.4.4.1.1 General 6.4.4.1.2 Duct and Plenum Insulation |
89 | 6.4.4.1.3 Piping Insulation 6.4.4.1.4 Sensible Heating Panel Insulation 6.4.4.1.5 Radiant Floor Heating 6.4.4.2 Ductwork and Plenum Leakage 6.4.4.2.1 Duct Sealing 6.4.4.2.2 Duct Leakage Tests |
90 | 6.4.5 Walk-In Coolers and Walk-In Freezers 6.4.6 Refrigerated Display Case |
91 | 6.5 Prescriptive Path 6.5.1 Economizers |
92 | 6.5.1.1 Air Economizers 6.5.1.1.1 Design Capacity 6.5.1.1.2 Control Signal |
93 | 6.5.1.1.3 High-Limit Shutoff 6.5.1.1.4 Dampers 6.5.1.1.5 Relief of Excess Outdoor Air 6.5.1.1.6 Sensor Accuracy 6.5.1.2 Fluid Economizers 6.5.1.2.1 Design Capacity |
94 | 6.5.1.2.2 Maximum Hydronic Pressure Drop 6.5.1.3 Integrated Economizer Control |
95 | 6.5.1.4 Economizer Heating System Impact 6.5.1.5 Economizer Humidification System Impact 6.5.2 Simultaneous Heating and Cooling Limitation 6.5.2.1 Zone Controls |
96 | 6.5.2.1.1 Supply Air Temperature Reheat Limit 6.5.2.2 Hydronic System Controls 6.5.2.2.1 Three-Pipe System 6.5.2.2.2 Two-Pipe Changeover System 6.5.2.2.3 Hydronic (Water Loop) Heat Pump Systems |
97 | 6.5.2.3 Dehumidification 6.5.2.4 Humidification 6.5.2.4.1 6.5.2.4.2 |
98 | 6.5.2.5 Preheat Coils 6.5.2.6 Ventilation Air Heating Control 6.5.3 Air System Design and Control 6.5.3.1 Fan System Power and Efficiency 6.5.3.1.1 6.5.3.1.2 Motor Nameplate Horsepower 6.5.3.1.3 Fan Efficiency |
99 | 6.5.3.2 Fan Control 6.5.3.2.1 Supply Fan Airflow Control |
100 | 6.5.3.2.2 VAV Static Pressure Sensor Location 6.5.3.2.3 VAV Set-Point Reset 6.5.3.2.4 Return and Relief Fan Control |
101 | 6.5.3.3 Multiple-Zone VAV System Ventilation Optimization Control 6.5.3.4 Parallel-Flow Fan-Powered VAV Air Terminal Control 6.5.3.5 Supply Air Temperature Reset Controls 6.5.3.6 Fractional Horsepower Fan Motors |
102 | 6.5.3.7 Ventilation Design 6.5.4 Hydronic System Design and Control 6.5.4.1 Boiler Turndown 6.5.4.2 Hydronic Variable Flow Systems |
103 | 6.5.4.3 Chiller and Boiler Isolation 6.5.4.3.1 6.5.4.3.2 6.5.4.4 Chilled- and Hot-Water Temperature Reset Controls 6.5.4.5 Hydronic (Water Loop) Heat Pumps and Water-Cooled Unitary Air Conditioners 6.5.4.5.1 |
104 | 6.5.4.5.2 6.5.4.6 Pipe Sizing 6.5.4.7 Chilled-Water Coil Selection |
105 | 6.5.5 Heat-Rejection Equipment 6.5.5.1 General 6.5.5.2 Fan Speed Control 6.5.5.2.1 6.5.5.2.2 6.5.5.3 Limitation on Centrifugal Fan Open-Circuit Cooling Towers 6.5.5.4 Tower Flow Turndown 6.5.6 Energy Recovery |
106 | 6.5.6.1 Exhaust Air Energy Recovery 6.5.6.2 Heat Recovery for Service Water Heating 6.5.6.2.1 6.5.6.2.2 |
107 | 6.5.7 Exhaust Systems 6.5.7.1 Transfer Air |
108 | 6.5.7.2 Kitchen Exhaust Systems 6.5.7.2.1 6.5.7.2.2 6.5.7.2.3 6.5.7.2.4 Performance Testing |
109 | 6.5.7.3 Laboratory Exhaust Systems 6.5.8 Radiant Heating Systems 6.5.8.1 Heating Unenclosed Spaces 6.5.8.2 Heating Enclosed Spaces 6.5.9 Hot-Gas Bypass Limitation |
110 | 6.5.10 Door Switches 6.5.11 Refrigeration Systems 6.5.11.1 Condensers Serving Refrigeration Systems |
111 | 6.5.11.2 Compressor Systems 6.6 Alternative Compliance Path 6.6.1 Computer Rooms Systems |
112 | 6.6.1.1 6.6.1.2 6.6.1.3 6.7 Submittals 6.7.1 General 6.7.2 Completion Requirements 6.7.2.1 Drawings 6.7.2.2 Manuals |
113 | 6.7.2.3 System Balancing 6.7.2.3.1 General 6.7.2.3.2 Air System Balancing 6.7.2.3.3 Hydronic System Balancing 6.7.2.4 System Commissioning 6.8 Minimum Equipment Efficiency Tables 6.8.1 Minimum Efficiency Requirement Listed Equipment— Standard Rating and Operating Conditions 6.8.2 Duct Insulation Tables 6.8.3 Piping Insulation Tables |
133 | 7. Service Water Heating 7.1 General 7.1.1 Service Water-Heating Scope 7.1.1.1 New Buildings 7.1.1.2 Additions to Existing Buildings 7.1.1.3 Alterations to Existing Buildings 7.2 Compliance Paths 7.2.1 Compliance 7.2.2 |
134 | 7.3 Simplified/Small Building Option (Not Used) 7.4 Mandatory Provisions 7.4.1 Load Calculations 7.4.2 Equipment Efficiency 7.4.3 Service Hot-Water Piping Insulation 7.4.4 Service Water-Heating System Controls 7.4.4.1 Temperature Controls 7.4.4.2 Temperature Maintenance Controls 7.4.4.3 Outlet Temperature Controls |
135 | 7.4.4.4 Circulating Pump Controls 7.4.5 Pools 7.4.5.1 Pool Heaters 7.4.5.2 Pool Covers 7.4.5.3 Time Switches 7.4.6 Heat Traps 7.5 Prescriptive Path 7.5.1 Space Heating and Service Water Heating |
136 | 7.5.2 Service Water-Heating Equipment 7.5.3 Buildings with High-Capacity Service Water-Heating Systems 7.6 Alternative Compliance Path (Not Used) 7.7 Submittals 7.7.1 General 7.8 Product Information |
139 | 8. Power 8.1 General 8.1.1 Scope 8.1.2 New Buildings 8.1.3 Addition to Existing Buildings 8.1.4 Alterations to Existing Buildings 8.1.4.1 8.1.4.2 8.2 Compliance Paths 8.2.1 Compliance 8.3 Simplified/Small Building Option (Not Used) 8.4 Mandatory Provisions 8.4.1 Voltage Drop |
140 | 8.4.2 Automatic Receptacle Control 8.4.3 Electrical Energy Monitoring 8.4.3.1 Monitoring 8.4.3.2 Recording and Reporting |
141 | 8.4.4 Low-Voltage Dry-Type Distribution Transformers |
142 | 8.5 Prescriptive Path (Not Used) 8.6 Alternative Compliance Path (Not Used) 8.7 Submittals 8.7.1 Drawings 8.7.2 Manuals 8.8 Product Information (Not Used) |
143 | 9. Lighting 9.1 General 9.1.1 Scope 9.1.2 Lighting Alterations 9.1.3 Installed Lighting Power |
144 | 9.1.4 Interior and Exterior Luminaire Wattage 9.1.5 Climate 9.2 Compliance 9.2.1 Compliance Paths 9.2.2 Prescriptive Requirements 9.2.2.1 Building Area Method 9.2.2.2 Space-by-Space Method |
145 | 9.2.2.3 Interior Lighting Power 9.3 (Not Used) 9.4 Mandatory Provisions 9.4.1 Lighting Control 9.4.1.1 Interior Lighting Controls |
148 | 9.4.1.2 Parking Garage Lighting Control 9.4.1.3 Special Applications |
149 | 9.4.1.4 Exterior Lighting Control |
150 | 9.4.2 Exterior Building Lighting Power 9.4.3 Functional Testing |
153 | 9.4.4 Dwelling Units 9.5 Building Area Method Compliance Path 9.5.1 Building Area Method of Calculating Interior Lighting Power Allowance 9.6 Alternative Compliance Path: Space-by-Space Method 9.6.1 Space-by-Space Method of Calculating Interior Lighting Power Allowance |
154 | 9.6.2 Additional Interior Lighting Power 9.6.3 Additional Interior Lighting Power Using Nonmandatory Controls |
163 | 9.6.4 Room Geometry Adjustment 9.7 Submittals 9.7.1 General 9.7.2 Completion Requirements 9.7.2.1 Drawings |
164 | 9.7.2.2 Manuals 9.7.2.3 Daylighting Documentation 9.8 Product Information (Not Used) |
165 | 10. Other Equipment 10.1 General 10.1.1 Scope 10.1.1.1 New Buildings 10.1.1.2 Additions to Existing Buildings 10.1.1.3 Alterations to Existing Buildings 10.1.1.3.1 10.1.1.3.2 10.2 Compliance Paths 10.2.1 Compliance 10.2.2 10.3 Simplified/Small Building Option (Not Used) 10.4 Mandatory Provisions |
166 | 10.4.1 Electric Motors 10.4.2 Service Water Pressure-Booster Systems 10.4.3 Elevators 10.4.3.1 Lighting 10.4.3.2 Ventilation Power Limitation 10.4.3.3 Standby Mode 10.4.3.4 Design Documents |
167 | 10.4.4 Escalators and Moving Walks 10.4.5 Whole-Building Energy Monitoring 10.4.5.1 Monitoring 10.4.5.2 Recording and Reporting 10.5 Prescriptive Compliance Path (Not Used) 10.6 Alternative Compliance Path (Not Used) 10.7 Submittals (Not Used) 10.8 Product Information |
173 | 11. Energy Cost Budget Method 11.1 General 11.1.1 Energy Cost Budget Method Scope 11.1.2 Trade-Offs Limited to Building Permit 11.1.3 Envelope Limitation 11.2 Compliance 11.3 Simplified Option (Not Used) |
174 | 11.4 Simulation General Requirements 11.4.1 Simulation Program 11.4.1.1 11.4.1.2 11.4.1.3 11.4.1.4 11.4.2 Climatic Data 11.4.3 Renewable, Recovered, and Purchased Energy 11.4.3.1 On-Site Renewable Energy and Site-Recovered Energy |
175 | 11.4.3.2 Annual Energy Costs 11.4.4 Compliance Calculations 11.4.5 Exceptional Calculation Methods 11.5 Calculation of Design Energy Cost and Energy Cost Budget 11.5.1 11.5.2 HVAC Systems |
177 | 11.6 Alternative Compliance Path (Not Used) 11.7 Documentation Requirements 11.8 Product Information (Not Used) |
191 | Normative Appendix A—Rated R-Value of Insulation and Assembly U-Factor, C-Factor, and F-Factor Determinations A1 General A1.1 Precalculated Assembly U-Factors, C-Factors, F-Factors, or Heat Capacities A1.2 Applicant-Determined Assembly U-Factors, C-Factors, F-Factors, or Heat Capacities A2 Roofs A2.1 General A2.2 Roofs with Insulation Entirely Above Deck A2.2.1 General A2.2.2 Rated R-Value of Insulation A2.2.3 U-Factor |
192 | A2.3 Metal Building Roofs A2.3.1 General A2.3.2 Rated R-Value of Insulation A2.3.2.1 Single Layer A2.3.2.2 Double Layer A2.3.2.3 Continuous Insulation A2.3.2.4 Liner System (Ls) A2.3.2.5 Filled Cavity A2.3.3 U-Factors for Metal Building Roofs A2.4 Attic Roofs with Wood Joists A2.4.1 General |
193 | A2.4.2 Rated R-Value of Insulation A2.4.2.1 A2.4.2.2 A2.4.2.3 A2.4.2.4 A2.4.3 U-Factors for Attic Roofs with Wood Joists A2.5 Attic Roofs with Steel Joists A2.5.1 General A2.5.2 |
198 | A3 Above-Grade Walls A3.1 Mass Wall A3.1.1 General A3.1.2 Mass Wall Rated R-Value of Insulation A3.1.2.1 A3.1.2.2 A3.1.2.3 A3.1.2.4 A3.1.3 Mass Wall U-Factor A3.1.3.1 A3.1.3.2 Determination of Mass Wall U-Factors |
199 | A3.2 Metal Building Walls A3.2.1 General A3.2.2 Rated R-Value of Insulation for Metal Building Walls A3.2.2.1 Single-Layer Compressed A3.2.2.2 Continuous Insulation A3.2.2.3 Single-Layer in Cavity A3.2.2.4 Double-Layer A3.2.3 U-Factors for Metal Building Walls A3.3 Steel-Framed Walls A3.3.1 General |
200 | A3.3.2 Rated R-Value of Insulation for Steel-Framed Walls A3.3.2.1 A3.3.2.2 A3.3.2.3 A3.3.3 U-Factors for Steel-Framed Walls A3.3.3.1 A3.3.3.2 A3.3.3.3 A3.3.3.4 A3.4 Wood-Framed Walls A3.4.1 General |
201 | A3.4.2 Rated R-value of Insulation for Wood-Framed and Other Walls A3.4.2.1 A3.4.2.2 A3.4.3 U-Factors for Wood-Framed Walls A3.4.3.1 A3.4.3.2 A3.4.3.3 A3.4.3.4 |
215 | A4 Below-Grade Walls A4.1 General A4.2 C-Factors for Below-Grade Walls A4.2.1 A4.2.2 A4.2.3 A5 Floors A5.1 General A5.2 Mass Floors A5.2.1 General |
216 | A5.2.2 Rated R-Value of Insulation for Mass Floors A5.2.2.1 A5.2.2.2 A5.2.2.3 A5.2.2.4 A5.2.3 U-Factors for Mass Floors A5.2.3.1 A5.2.3.2 A5.3 Steel-Joist Floors A5.3.1 General A5.3.2 Rated R-Value of Insulation for Steel-Joist Floors A5.3.2.1 A5.3.2.2 A5.3.3 U-Factors for Steel-Joist Floors A5.3.3.1 A5.3.3.2 A5.4 Wood-Framed and Other Floors A5.4.1 General |
217 | A5.4.2 Rated R-Value of Insulation for Wood-Framed and Other Floors A5.4.2.1 A5.4.2.2 A5.4.3 U-Factors for Wood-Framed Floors A5.4.3.1 A5.4.3.2 A6 Slab-on-Grade Floors A6.1 General A6.2 Rated R-Value of Insulation for Slab-on-Grade Floors A6.2.1 A6.2.2 A6.2.3 |
218 | A6.3 F-Factors for Slab-on-Grade Floors A6.3.1 A6.3.2 |
224 | A7 Opaque Doors A7.1 Unlabeled Opaque Doors A8 Fenestration A8.1 Unlabeled Skylights A8.2 Unlabeled Vertical Fenestration |
229 | A9 Determination of Alternate Assembly U-Factors, C-Factors, F-Factors, or Heat Capacities A9.1 General A9.2 Required Procedures |
230 | A9.3 Testing Procedures A9.3.1 Building Material Thermal Properties A9.3.2 Assembly U-Factors A9.4 Calculation Procedures and Assumptions A9.4.1 Air Films A9.4.1.1 A9.4.1.2 A9.4.1.3 A9.4.2 Air Spaces |
231 | A9.4.3 Insulation R-Values A9.4.4 Building Material Thermal Properties A9.4.5 Building Material Heat Capacities A9.4.6 Metal Building U-Factor Equations |
232 | A9.4.6.1 Single-Layer Roof and Single-Layer Compressed Wall |
234 | A9.4.6.2 Double-Layer Roof |
237 | A9.4.6.3 Single-Layer in Cavity and Double-Layer Walls |
247 | Informative Appendix B—(Retained for Future Use) |
249 | Normative Appendix C—Methodology for Building Envelope Trade-Off Option in Section 5.6 C1 Minimum Information C1.1 At the Building Level C1.2 At the Exterior and Semiexterior Surface Level C1.2.1 For Roofs C1.2.2 For Above-Grade Walls C1.2.3 For Below-Grade Walls C1.2.4 For Floors C1.2.5 For Slab-on-Grade Floors C1.2.6 For Uninsulated Assemblies C1.3 For Opaque Doors |
250 | C1.4 For Fenestration C2 Output Requirements C2.1 C2.2 C2.3 C2.4 C2.5 C2.6 C2.7 C2.8 C3 Simulation General Requirements C3.1 Simulation Program |
251 | C3.1.1 C3.1.2 C3.1.3 C3.1.4 C3.2 Climatic Data C3.2.1 Surface Exposure C3.3 Purchased Energy Rates |
252 | C3.4 Compliance Calculations C3.5 Calculation of Proposed Envelope Performance Factor C3.5.1 Space-Conditioning C3.5.2 Model Geometry and Thermal Zones |
253 | C3.5.3 Daylight Area and Photosensor Location C3.5.4 Schedules C3.5.5 Building Envelope C3.5.5.1 Shading |
254 | C3.5.5.2 Dynamic Glazing C3.5.5.3 Air Leakage C3.5.5.3.1 Infiltration Schedule C3.5.6 Interior Surfaces C3.5.7 Lighting |
255 | C3.5.8 HVAC Systems C3.5.9 Miscellaneous Loads C3.5.10 Occupant Density C3.5.11 Heat Gain from Occupants C3.6 Calculation of Base Envelope Performance Factor |
257 | Informative Appendix D—(Retained for Future Use) |
259 | Informative Appendix E—Informative References |
263 | Informative Appendix F—U.S. Department of Energy Minimum Energy Efficiency Requirements F1 DOE Minimum Energy Efficiency Requirements for Single-Phase Air Conditioners and Heat Pumps F2 DOE Minimum Energy Efficiency Requirements for Water Heaters F3 DOE Minimum Energy Efficiency Requirements for Pool Heaters |
267 | Normative Appendix G—Performance Rating Method G1 General G1.1 Performance Rating Method Scope G1.2 Performance Rating G1.2.1 Mandatory Provisions G1.2.2 Performance Rating Calculation G1.3 Documentation Requirements |
268 | G2 Simulation General Requirements G2.1 Performance Calculations |
269 | G2.2 Simulation Program G2.2.1 G2.2.2 G2.2.3 G2.2.4 G2.3 Climatic Data G2.4 Renewable, Recovered, and Purchased Energy G2.4.1 On-Site Renewable Energy and Site-Recovered Energy |
278 | G2.4.2 Annual Energy Costs G2.5 Exceptional Calculation Methods G3 Calculation of the Proposed Design and Baseline Building Performance G3.1 Building Performance Calculations G3.1.1 Baseline HVAC System Type and Description |
279 | G3.1.1.1 Purchased Heat G3.1.1.2 Purchased Chilled Water G3.1.1.3 Baseline HVAC System Requirements for Systems Utilizing Purchased Chilled Water and/or Purchased Heat G3.1.1.3.1 Purchased Heat Only |
280 | G3.1.1.3.2 Purchased Chilled Water Only G3.1.1.3.3 Purchased Chilled Water and Purchased Heat G3.1.1.3.4 On-Site Distribution Pumps G3.1.1.4 Modeling Building Envelope Infiltration |
281 | G3.1.2 General Baseline HVAC System Requirements G3.1.2.1 Equipment Efficiencies G3.1.2.2 Equipment Capacities G3.1.2.2.1 Sizing Runs |
282 | G3.1.2.3 Unmet Loads G3.1.2.4 Fan System Operation G3.1.2.5 Ventilation G3.1.2.6 Economizers |
283 | G3.1.2.6.1 Computer Room Economizers G3.1.2.7 Economizer High-Limit Shutoff G3.1.2.8 Design Airflow Rates G3.1.2.8.1 Baseline All System Types Except System Types 9 and 10 G3.1.2.8.2 Baseline System Types 9 and 10 G3.1.2.9 System Fan Power |
284 | G3.1.2.9.1 G3.1.2.10 Exhaust Air Energy Recovery G3.1.3 System-Specific Baseline HVAC System Requirements G3.1.3.1 Heat Pumps (Systems 2 and 4) |
285 | G3.1.3.2 Type and Number of Boilers (Systems 1, 5, and 7) G3.1.3.3 Hot-Water Supply Temperature (Systems 1, 5, 7, and 12) G3.1.3.4 Hot-Water Supply Temperature Reset (Systems 1, 5, 7, 11, and 12) G3.1.3.5 Hot-Water Pumps G3.1.3.6 Piping Losses (Systems 1, 5, 7, 8, and 11) G3.1.3.7 Type and Number of Chillers (Systems 7, 8, 11, 12, and 13) G3.1.3.8 Chilled-Water Design Supply Temperature (Systems 7, 8, 11, 12, and 13) G3.1.3.9 Chilled-Water Supply Temperature Reset (Systems 7, 8, 11, 12, and 13) |
286 | G3.1.3.10 Chilled-Water Pumps (Systems 7, 8, and 11) G3.1.3.11 Heat Rejection (Systems 7, 8, 9, 12, and 13) G3.1.3.12 Supply Air Temperature Reset (Systems 5 through 8) G3.1.3.13 VAV Minimum Flow Set Points (Systems 5 and 7) |
287 | G3.1.3.14 Fan Power and Control (Systems 6 and 8) G3.1.3.15 VAV Fan Part-Load Performance (Systems 5 through 8 and 11) G3.1.3.16 Computer Room Equipment Schedules G3.1.3.17 System 11 Supply Air Temperature and Fan Control G3.1.3.18 Dehumidification (Systems 3 through 8 and 11, 12, and 13) G3.1.3.19 Preheat Coils (Systems 5 through 8) |
309 | Informative Appendix H—Addenda Description Information |
319 | Annex 1—Reference Standard Reproduction Annex—ASHRAE Standard 169 |